MAIN ENGINE D.O. TO H.F.O. CHANGING PROCEDUR

PREPARATION

  1. IT IS TO BE CONFIRMED THAT FO SERVICE TANK, FO TEMP IS ABOUT 750 C.
  2. OPEN THE STEAM TRACING FOR M/E F.O.  LINES. 
  3. M/E FO HEATER AND VISCOCITY CONTROLLER TO BE PREPARED FOR WORKING.

PROCEDURE.


  1. M/E LOAD SHOULD BE AROUND 75% OF THE NORMAL OUTPUT (i.e. AROUND 64%).
  2. OPEN VISCO CONTROLLER STEAM INLET VALVE  AND OUTLET VALVE .
  3. M/E HEATER INLET AND OUTLET STEAM VALVE..
  4. BY OPERATING THE VISCOCITY CONTROLLER MANUALLY IN THE ENGINE CONTROL ROOM, D.O. IN THE SYSTEM SOUL BE HEATED TO 60 – 800C, GRADUALLY AT THE RATE 20C PER MINUTE.
  5. IT IS TO BE CONFIRMED THAT THE D.O. TEMP IN THE SYSTEM IS 60 – 800C.
  6. OPEN THE H.F.O VALVE , AND SHUT D.O. INLET VALVE .
  7. AFTER THE HFO IN THE SYSTEM IS TO BE HEATED UP TO THE PREDETERMINED VISCOCITY 10 TO 14 Cst AT RATE 20C PER Min. BY CONTROLLING VISCOCITY MANUALLY FROM THE E.C.R.
  8. ONCE THE REQUIRED VISCOCITY OF HFO ATTAINED – 14 Cst, CHANGE THE VISCO CONTROLL TO AUTO MODE (VISCO MODE).